Project Overview
Power EM designed and implemented an integrated HVAC system for a 200-bed specialty hospital, including 10 operating theatres, ICU/CCU, isolation wards, laboratories, and administrative areas.
Special Technical Requirements
Operating Theatres
- Laminar Flow system with HEPA H14 filtration
- Positive pressure +15 Pa vs corridors
- Temperature: 18-24°C, Humidity: 45-60% RH
- ACH: 20-25 (30% fresh + 70% recirculated)
Results Achieved
| Indicator | Target | Achieved |
|---|---|---|
| Energy Consumption | < 0.65 kW/ton | 0.58 kW/ton ✅ |
| Air Quality | ISO Class 5 | ISO Class 4 ✅ |