Introduction
Selecting the right central HVAC system is one of the most critical engineering decisions during the design phase. A wrong decision means high energy consumption, costly maintenance, and occupant discomfort.
Step 1: Heat Load Calculation
Heat load is calculated per ASHRAE Handbook of Fundamentals and includes:
- Internal loads: electrical equipment, lighting, occupant heat
- External loads: solar radiation through glazing, outdoor temperatures
- Ventilation loads: fresh air requirements per ASHRAE 62.1

Central System Types
1. Chiller Systems
Ideal for buildings exceeding 5,000 m². Chills water distributed to air handling units on each floor. Efficiency ranges 0.5 – 0.7 kW/ton.
2. VRF/VRV Systems
Uses variable refrigerant flow directly to indoor units. Suitable for mid-size buildings with zone-by-zone control. High efficiency makes them the most demanded in modern markets.

Efficiency Standards
| System | Efficiency | Standard |
|---|---|---|
| Chiller | COP ≥ 5.5 | ASHRAE 90.1 |
| VRF/VRV | IPLV ≥ 4.0 | AHRI 1230 |
| DX | SEER ≥ 14 | DOE |